2. Function and features
The unit monitors linear, pendulum, pulsating and rotating movements. It
receives pulses from external sensors, measures the pulse interval and calcu-
lates the input frequency (=actual value), compares it with the preset switch
point (preset value) and switches the output in accordance with the preset
parameters.
Setting range: 5 ... 5000 pulses/min. or 10 ... 10 000 pulses/min.
Maximum input frequency: 15000 pulses/min. (corresponds to 250 Hz). If this
value is exceeded, the D100 switches as for input frequency = 0.
Minimum pulse length: 2ms.
Pulse pick-ups: 3-wire DC PNP, 2-wire AC/DC, 2-wire quadronorm,
incremental encoders, mechanical switches.
Signal level for the D100 pulse input: minimum 14 V.
The monitor has a one-channel design. If the outputs of two or
several units are electrically connected in order to achieve a
redundant circuit, they can also be used for safetey tasks. The technical
standards that apply to the respective application have to be taken into
account.
3. Mounting
The control cabinet should be installed in accordance with local and
national rules and regulations.
Mount the unit on a DIN rail or by means of a mounting base. Once mounted
leave enough space between the unit and the top and bottom of the control
cabinet (to enable air circulation and to avoid excessive heating).
Mounting of the pulse pick-ups:
Adhere to the mounting instructions of
the manufacturer.
For optimum functioning of inductive
switches the following dimensions
should be adhered to:
B=2 × A
C=½ × S
n
18
PULSE EVALUATION SYSTEM D100
C
A
A
B
A